Technical description
28 DRYPOINT
®
RS 15 – 1700 HP50 NA
5.19. DMC15 Electronic Instrument (Air Dryer Controller)
set
Button -
access the set-up.
Button -
value increment.
Green LED -
glowing = power on.
Yellow LED -
Not used
Yellow LED -
glowing = condenser fan on.
DMC15
ON
sec - min
set
P
Q
S
0
0
1
4
DISPLAY
The DMC15 electronic controller performs the following functions : it shows the current operating DewPoint through the
digital led display which is detected from the (T1) probe located at the end of the evaporator, while a second (T2) probe,
located on the discharge side of the condenser, activates the relevant fan.
OPERATION - During the dryer operation, the LED is on.
Thermometer
-
The 10 LED display indicates the current operating DewPoint, shown by means of a two colours (green
- red) bar over the display itself.
Green section - operating conditions ensuring an optimal DewPoint;
Red section - DewPoint of the dryer too high, the dryer is working with elevated thermal load (high inlet air
temperature, high ambient temperature, etc.). The treatment of the compressed air may be improper.
Too high DewPoint temperature, value exceeding the upper limit of the instrument range, is indicated by the intermittent
flashing of the last LED; whereas the intermittent flashing of the first LED shows too low DewPoint temperature.
A possible (T1) probe failure is indicated by the intermittent flashing of the first and last LED of the display, whereas the
dryer keeps on working correctly.
Thermostat - The fan condenser is activated when the condensate temperature reaches or exceeds 95°F (35°C)
(FANON) - LED on - and it is deactivated when the temperature goes down to 86°F (30°C) (FANON - Hys) - LED
off. In case of (T2) probe failure, the fun will run continuously and the LED will intermittent flash.
SET-UP - The DMC15 is adjusted during the final test of the dryer. In case of particular requirements concerning the
operation management, the user can change the setting of the programmed parameters.
The parameters which can be set up are the following :
FANON - activation temperature of condenser fan. It is adjustable inside the following range of values, with step of
1.8°F (1°K); whereas the Hys hysteresis is fixed and equal to -9°F (-5ºK).
TON – Not used
TOFF - Not used
To access the set-up, keep the button
set
pressed for at least 2 seconds; LED flashing confirms the
command. First appears the (FANON) parameter; to access the other parameters, press sequentially the
set
button.
To change the value of the selected parameter, keep the
set
button pressed and operate on button ; the
current value is shown on the LED display. For the value range and the resolution (value of each single LED), see the
following table :
Parameter
Description Display Value range Resolution Set
value
FANON
Activation temperature of
condenser fan
Synchronous flashing
LED + LED
(87.8 … 104 °F)
(31 … 40 °C)
1.8°F
K
95 °F
35°C
TON Not used
Synchronous flashing
LED + LED
1 - 10 sec 1 sec -
TOFF Not used
Non-Synchronous
flashing
LED + LED
1 - 10 min 1 min -
To exit the set-up condition in any moment, press the
button. If no operations are performed for 2 minutes, the
system automatically exits the set-up condition.