Analogue current signal
Data Display DD109 11
10.2 Alarm connection
NC and COM are closed in case of:
- alarm
- power failure
- sensor break
11 Analogue current signal
The flow sensor and the DP sensor offer the possibility to provide the measured values as analogue current
signal 4…20 mA for further process treatment . The connection schemes have already been set for this.
11.1 Analogue current signal flow sensor
Terminal G "Flow sensor“
The flow sensor is connected to the clamps
at terminal G according to the scheme
indicated at the left. The analogue signal
(4...20mA) is at clamp 1 and 3 and can be
tapped if required (maximum burden
< 500 Ohm)
11.2 Analogue current signal DPsensor
Terminal I „DP sensor“
The DP sensor is connected to the clamps
at terminal I according to the scheme
indicated at the left. The analogue signal
(4...20mA) is at clamp 1 and 2 and can be
tapped if required (maximum burden
< 500 Ohm). If the analogue signal is not
used a wire jumper has to be inserted here
obligatorily (factory-provided)